C200-06400470 – 3P/380VAC- 22kW/30kW
Công suất : | 22kW / 30 kW |
Điện áp : | 3P -380VAC |
Dòng điện định mức motor: | 47A / 63A |
Hãng sản xuất : | Control Techniques ( 1 thương hiệu của Nidec ) |
Xuất xứ: | Anh Quốc ( United Kingdom ) |
Bảo hành : | 24 tháng |
Cách đọc mã hàng C200 | |
Đặc tính kỹ thuật | |
Ambient Operating Temperature | Size 1 – 4: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. | Operation to 60°C (140°F) with de-rating Size 5 – 9: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. | Operation to 55°C (131°F) with de-rating |
Cooling method | Forced convection |
Humidity | 95 % non-condensing at 40 °C (104 °F) |
Storage Temperature | Size 1 – 4: -40°C to 60°C (-40°F to 140°F) — 24 months Max. Size 5 – 9: -40°C to 55°C (-40°F to 131°F) — 24 months Max. |
Altitude | De-rate the continuous output current by 1% for every 100 m (328 ft) above 1000 m (3,280 ft) to a maximum of 3000 m (9,840 ft) |
Vibration | Tested in accordance with IEC 60068-2-64 and IEC 60068-2-6 |
Mechanical Shock | Tested in accordance with IEC 60068-2-27 and IEC 60068-2-29 |
Enclosure Rating | IP20, NEMA 1 conduit kits available |
Electromagnetic Capability | IEC/ EN 61800-3 Immunity and Emissions EN 61000-6-2: Immunity for industrial environments EN 61000-6-4: Emissions for industrial environments EN 61000-3-2: Harmonic current emissions An EMC data sheet is available on request |
RoHS | Complies with the Restriction of Hazardous Substances Directive (2011/65/EU) |
AC Supply Requirements | |
Voltage | 100 V models: 100 to 120 Vac ±10% 200 V models: 200 to 240 Vac ±10% 400 V models: 380 to 480 Vac ±10% |
Phase | 1Ø and 3Ø (Model dependent) |
Maximum Supply Imbalance | 2% negative phase sequence, 3% voltage imbalance between phases |
Input Frequency | 45 to 66 Hz |
Input Displacement Power Factor | 0.97 |
Control | |
Switching Frequency | Size 1 – 4: 0.667, 1, 2, 3, 4, 6, 8 12 & 16 kHz Size 5 – 9: 2, 3, 4, 6, 8 12 & 16 kHz |
Output Frequency Range | 0 to 550 Hz |
Frequency Accuracy | ±0.02% of full scale |
Frequency Resolution | 0.01 Hz |
Analog Input Resolution | Voltage mode: 11 bits (unipolar) Current mode: 11 bits |
Braking | Dynamic braking transistor included, requires external resistor |
Protection | |
DC Bus Undervoltage Trip | 100 V models: 175 Vdc 200 V models: 175 Vdc 400 V models: 330 Vdc |
DC Bus Overvoltage Trip | Frame sizes 1 – 4: 100 V models: 510 Vdc 200 V models: 510 Vdc 400V models: 870 Vdc |
Frame size 5 – 9: 200V models: 415 Vdc 400 V models: 830 Vdc | |
Drive Overload Trip | Programmable: Default settings: 180% for 3s, 150% for 60s |
Instantaneous Overcurrent Trip | 220% of rated motor current |
Phase Loss Trip | DC bus ripple threshold exceeded |
Over-temperature Trip | Drive heatsink temperature exceeds 95°C (203°F) |
Short Circuit Trip | Protects against output phase-to-phase fault |
Ground Fault Trip | Protects against output phase-to-ground fault |
Motor Thermal Trip | Electronically protects the motor from overheating due to loading conditions |
Approval & Listings | |
UL, cUL | UL file NMMS/8: E171230 |
CE | CE approval |
EU | TheseSản phẩms comply with the Restriction of Hazardous Substances Directive (2011/65/EU), the Low Voltage Directive (2014/35/ EU) and the Electromagnetic Compatibility Directive, (2014/30/EU). |
RCM | RCM Registered supplier No. 12003815281 |
ISO | Manufacturing facilities comply with ISO 9001:2015 and ISO 14001 |
TÜV | C300 models only: The Safe Torque Off (STO) function may be used as a safety component of a machine. Type examination certificates by TÜV Rheinland: Frame sizes 1 – 4: No. 01/205/5383.03/18 Frame sizes 5 – 9: No. 01/205/5387.02/18 Functional safety parameters: EN ISO 13849-1 – Cat 4, PLe EN61800-5-2/EN62061/IEC 61508 – SIL 3 UL functional safety approval: FSPC E171230 |
Chúng tôi đảm bảo nhập hàng từ những nơi đáng tin cậy, sản phẩm chính hãng với chất lượng đúng tiêu chuẩn và cấu trúc chắc chắn, độ chính xác cao , thiết kế chính xác, chống ăn mòn, chống mài mòn và tuổi thọ dài.
Đánh giá
Chưa có đánh giá nào.